· Product Introduction
The SPC series communication signal conversion modules are primarily designed for signal interference processing and conversion in industrial settings. Their core functions include ground loop isolation, electromagnetic interference elimination, enhanced circuit load capacity, and support for device signal sharing and monitoring. They are widely used in measurement and control systems and various automatic control systems across industries such as industrial automation, medical electronics, automotive manufacturing, power engineering, petrochemicals, aerospace, railways, and PLC applications.
The SPC8011-NA is an RS232 to RS485 signal repeater. It complies with the EIA/TIA RS485 standard, amplifying and isolating RS485 signals to extend communication distance. Employing high-speed opto-isolation protection, it addresses issues of signal relaying and isolation in complex electromagnetic environments. The module incorporates industrial-grade chips with superior anti-interference capabilities and features an intelligent directional circuit that automatically detects data flow direction. This ensures stable signals, secure and reliable data communication, and eliminates delay problems associated with serial signal transceiver switching.
This product requires a separate power supply and is mounted on a standard 35mm DIN rail, offering simple on-site installation and flexible use, suitable for a variety of field applications.
· Basic Parameters
Power Supply DC12~36V(DC24V recommended)
Current Consumption ≤50mA @DC24V
Power Protection Reverse Voltage <-40V
Isolation DC1500V (Master, Slave)
Insulation Resistance ≥100MΩ (Master, Slave)
Electromagnetic Compatibility Complies with GB/T182681 (IEC 6132-1)
Suitable Application RS232 to RS485 systems requiring extended communication distance
· Serial Port Parameters
Input Signal 1 x RS232
Output Signal 1 x RS485
Operating Mode RS232 asynchronous full-duplex
RS485 asynchronous half-duplex differential
Communication Protocol Independent of software protocol restrictions
Signal Level Standard RS485 differential level
Standard RS232 level
Load Capacity Single RS485 interface supports up to 32 nodes
Distance between nodes ≤ 10 m
Baud Rate 300 – 230,400 bps (Auto-adaptive)
Transmission Delay < 10uS
Protection Rating RS232: ±15 kV ESD RS485: 600W TVS
Communication distance RS232: 15 m (typical) RS485: 1200 m (typical)
· Environmental Conditions
Operating Temperature -40℃~+80℃
Storage Temperature -40℃~+85℃
Relative Humidity 10%~90%RH (non-condensing)
Atmospheric Pressure 80kPa~106kPa
· Product User Manual
PDF>>> SPC1020-KA Isolated USB to Serial Communication Module User Manual v1.0
PDF>>> SPC1021-KB Isolated USB to Serial Communication Module User Manual v1.0
PDF>>> SPC1022-NB Isolated USB to RS-232&RS-485 Converter Module User Manual v1.0
PDF>>> SPC1023-NB Isolated USB to RS-422&RS-485 Converter Module User Manual v1.0
PDF>>> SPC1030-KA USB to Serial Communication Module User Manual v1.0
PDF>>> SPC1031-KB USB to Serial Communication Module User Manual v1.0
PDF>>> SPC2040-MD Series 4 Channel RS-232 Serial Communication Server User Manual v1.2
PDF>>> SPC2080-MD Series 8 Channel RS-485 Serial Communication Server User Manual v1.2
PDF>>> SPC8010-NA Series RS-485 to RS-485 Repeater Isolated Module User Manual v1.2
PDF>>> SPC8011-NA Series RS-232 to RS-485 Repeater Isolated Module User Manual v1.2
PDF>>> SPC8040-MB 1 Master to 4 Slave Hub Communication Module User Manual v1.2
PDF>>> SPC8080-MB 1 Master to 8 Slave Hub Communication Module User Manual v1.2